Olkiluoto 3 – Nonlinear 3D Analysis of the Prestressed Containment

Nonlinear analysis of the prestressed concrete containment with steel liner for normal operation, pressure test, severe accident and overpressure up to failure.

Period: 2005 – 2006
Structure: prestressed concrete containment with steel liner, EPR unit
Software: ATENA

For the Olkiluoto 3 nuclear power plant in Finland, the Finnish nuclear safety authority (STUK) required nonlinear analyses of the prestressed concrete containment in addition to the standard design documents, as a basis for approving its construction. Phase I used an axisymmetric model of the base slab and gusset; Phase II used a 3D model of the whole containment for the release of the containment wall.

The 3D ATENA model included the containment wall, dome, ring and buttresses with the equipment hatch and other openings, the steel liner, the passive reinforcement and the individual prestressing tendons. Three load histories were analysed: normal operation, the pressure test up to 1.35 times the design pressure of 500 kPa, and a severe accident scenario with long-term heating of the wall. Following a meeting with the owner and the authority, the pressure test analysis was then continued up to failure.

Up to the test pressure the response was practically linear, with minor cracking only around tendon anchorages and the equipment hatch (crack widths below 0.06 mm). Significant nonlinearity started at about 0.9 MPa, the passive reinforcement began to yield at about 2.5 times the design pressure, and at about 3 times the design pressure the tendons near the ring yielded, which was taken as structural failure.

ATENA model of the Olkiluoto 3 containment
ATENA model of the containment.
Stresses in the horizontal prestressing tendons
Stresses in the horizontal prestressing tendons [MPa].